Posted by New Home Owner on March 12, 2007, 2:00 pm
Hello,
A few months ago, we purchased a 3 bedroom, 2 bath 1800 sq. ft.home
built in the mid-1960's. We've started to try to update the rooms
(stripping wallpaper, painting - nothing major), and this weekend,
decided to do the master bathroom. These bathrooms are tiny - maybe
6x5 feet - with tile covering most of the wall like wainscotting.
Above the sink was a mirror that we discovered was hiding an in-set
medicine cabinet, and a hole where an old wall sconce used to be
located. Above the toilet was a new wall sconce, and when I removed
it to strip the wallpaper, discovered that there was no junction box,
and that it had an extension wire spliced to the old junction box.
After much reading, I'm discovering several problems, and want to know
if the way I think I can fix it will be an approved repair.
First, the extension wire that was spliced from the original junction
box to their light fixture didn't have a ground wire, and the ground
wire is just "hanging out" in the junction box. Then, of course, they
didn't have a junction box, and the extension wire is 16 gauge (I
forgot to look at the circuit breaker to see what amp the circuit is,
but I'm betting it is 20). We thought we'd take this opportunity to
put a new 3-light sconce up above our medicine cabinet, but of course,
we can't use the old junction box because it's hidden behind the
medicine cabinet, and the original romex cable coming into the
junction box is not long enough to move to a new junction box.
Assuming the circuit is 20 amp, could I get new cable and splice the
white/white, black/black, and ground/ground inside the old junction
box, and then run the cable the 8 inches up the wall into a new "old
work" blue plastic junction box for a light fixture? I'd get a cover
for the old junction box, and our medicine cabinet would conceal it so
it would still be accessible as per code, but not viewable every day.
I'd then follow the lighting fixture guidlines for coupling the white/
white and black/black, but how would I handle the ground? The
instructions are to put the fixture's ground wire to the screw, but
then what would I do with the ground from the extension cable?
Thanks if you made it through this long question.
|

| |
Posted by Mike S. on March 12, 2007, 2:16 pm
What you want to do is fine, get rid of that 16 gauge wire, use a piece of
#12 romex, 2 conductors with a ground. Connect that in the junction box that
will be covered and concealed ( but accessible) behind the cabinet. Then run
the new wire inside the wall to the new box you install. Connect white to
white, black to black ( I'm assuming USA wiring, other countries are
different), and ground to ground and connect the ground to the fixtures
ground screw too, in other words all the grounds get connected together to
ground the metal of the fixture. I'm assuming all the wires are copper too,
if aluminum is involved it is different.
Make sure you do all this with the power off and use approved wire nuts,
etc, I'm assuming you have basic electrical wiring knowledge, this isn't
rocket science but you do need to have the basics, if not then ask again.
--
Mike S.
> Hello,
>
> A few months ago, we purchased a 3 bedroom, 2 bath 1800 sq. ft.home
> built in the mid-1960's. We've started to try to update the rooms
> (stripping wallpaper, painting - nothing major), and this weekend,
> decided to do the master bathroom. These bathrooms are tiny - maybe
> 6x5 feet - with tile covering most of the wall like wainscotting.
> Above the sink was a mirror that we discovered was hiding an in-set
> medicine cabinet, and a hole where an old wall sconce used to be
> located. Above the toilet was a new wall sconce, and when I removed
> it to strip the wallpaper, discovered that there was no junction box,
> and that it had an extension wire spliced to the old junction box.
> After much reading, I'm discovering several problems, and want to know
> if the way I think I can fix it will be an approved repair.
>
> First, the extension wire that was spliced from the original junction
> box to their light fixture didn't have a ground wire, and the ground
> wire is just "hanging out" in the junction box. Then, of course, they
> didn't have a junction box, and the extension wire is 16 gauge (I
> forgot to look at the circuit breaker to see what amp the circuit is,
> but I'm betting it is 20). We thought we'd take this opportunity to
> put a new 3-light sconce up above our medicine cabinet, but of course,
> we can't use the old junction box because it's hidden behind the
> medicine cabinet, and the original romex cable coming into the
> junction box is not long enough to move to a new junction box.
>
> Assuming the circuit is 20 amp, could I get new cable and splice the
> white/white, black/black, and ground/ground inside the old junction
> box, and then run the cable the 8 inches up the wall into a new "old
> work" blue plastic junction box for a light fixture? I'd get a cover
> for the old junction box, and our medicine cabinet would conceal it so
> it would still be accessible as per code, but not viewable every day.
> I'd then follow the lighting fixture guidlines for coupling the white/
> white and black/black, but how would I handle the ground? The
> instructions are to put the fixture's ground wire to the screw, but
> then what would I do with the ground from the extension cable?
>
> Thanks if you made it through this long question.
>
|
|
Posted by New Home Owner on March 12, 2007, 2:34 pm
> What you want to do is fine, get rid of that 16 gauge wire, use a piece of
> #12 romex, 2 conductors with a ground. Connect that in the junction box that
> will be covered and concealed ( but accessible) behind the cabinet. Then run
> the new wire inside the wall to the new box you install. Connect white to
> white, black to black ( I'm assuming USA wiring, other countries are
> different), and ground to ground and connect the ground to the fixtures
> ground screw too, in other words all the grounds get connected together to
> ground the metal of the fixture. I'm assuming all the wires are copper too,
> if aluminum is involved it is different.
>
> Make sure you do all this with the power off and use approved wire nuts,
> etc, I'm assuming you have basic electrical wiring knowledge, this isn't
> rocket science but you do need to have the basics, if not then ask again.
>
> --
>
> Mike S.
>
Thanks, Mike.
Yes, I am in the US and using copper wire. Your explanation of
handling the grounds helped - I knew I needed to connect them
together, but wasn't quite sure if connecting BOTH to the screw in the
fixture was the correct thing to do.
|
|
Posted by John Grabowski on March 12, 2007, 7:06 pm
> Hello,
>
> A few months ago, we purchased a 3 bedroom, 2 bath 1800 sq. ft.home
> built in the mid-1960's. We've started to try to update the rooms
> (stripping wallpaper, painting - nothing major), and this weekend,
> decided to do the master bathroom. These bathrooms are tiny - maybe
> 6x5 feet - with tile covering most of the wall like wainscotting.
> Above the sink was a mirror that we discovered was hiding an in-set
> medicine cabinet, and a hole where an old wall sconce used to be
> located. Above the toilet was a new wall sconce, and when I removed
> it to strip the wallpaper, discovered that there was no junction box,
> and that it had an extension wire spliced to the old junction box.
> After much reading, I'm discovering several problems, and want to know
> if the way I think I can fix it will be an approved repair.
>
> First, the extension wire that was spliced from the original junction
> box to their light fixture didn't have a ground wire, and the ground
> wire is just "hanging out" in the junction box. Then, of course, they
> didn't have a junction box, and the extension wire is 16 gauge (I
> forgot to look at the circuit breaker to see what amp the circuit is,
> but I'm betting it is 20). We thought we'd take this opportunity to
> put a new 3-light sconce up above our medicine cabinet, but of course,
> we can't use the old junction box because it's hidden behind the
> medicine cabinet, and the original romex cable coming into the
> junction box is not long enough to move to a new junction box.
>
> Assuming the circuit is 20 amp, could I get new cable and splice the
> white/white, black/black, and ground/ground inside the old junction
> box, and then run the cable the 8 inches up the wall into a new "old
> work" blue plastic junction box for a light fixture? I'd get a cover
> for the old junction box, and our medicine cabinet would conceal it so
> it would still be accessible as per code, but not viewable every day.
> I'd then follow the lighting fixture guidlines for coupling the white/
> white and black/black, but how would I handle the ground? The
> instructions are to put the fixture's ground wire to the screw, but
> then what would I do with the ground from the extension cable?
>
> Thanks if you made it through this long question.
In the 1960's it was not required to have a 20 amp circuit for the bathroom.
Nor for the kitchen for that matter. The current code does require a 20 amp
circuit for the bathroom GFCI outlet and you can leave the lighting on the
existing circuit. Since you are redoing the bathroom it is a good idea to
bring it up to current standards.
Your plan to redo the light box sounds good. Do what the other poster said
with the grounds.
|
|
Posted by New Home Owner on March 12, 2007, 9:58 pm
>
>
>
>
>
> > Hello,
>
> > A few months ago, we purchased a 3 bedroom, 2 bath 1800 sq. ft.home
> > built in the mid-1960's. We've started to try to update the rooms
> > (stripping wallpaper, painting - nothing major), and this weekend,
> > decided to do the master bathroom. These bathrooms are tiny - maybe
> > 6x5 feet - with tile covering most of the wall like wainscotting.
> > Above the sink was a mirror that we discovered was hiding an in-set
> > medicine cabinet, and a hole where an old wall sconce used to be
> > located. Above the toilet was a new wall sconce, and when I removed
> > it to strip the wallpaper, discovered that there was no junction box,
> > and that it had an extension wire spliced to the old junction box.
> > After much reading, I'm discovering several problems, and want to know
> > if the way I think I can fix it will be an approved repair.
>
> > First, the extension wire that was spliced from the original junction
> > box to their light fixture didn't have a ground wire, and the ground
> > wire is just "hanging out" in the junction box. Then, of course, they
> > didn't have a junction box, and the extension wire is 16 gauge (I
> > forgot to look at the circuit breaker to see what amp the circuit is,
> > but I'm betting it is 20). We thought we'd take this opportunity to
> > put a new 3-light sconce up above our medicine cabinet, but of course,
> > we can't use the old junction box because it's hidden behind the
> > medicine cabinet, and the original romex cable coming into the
> > junction box is not long enough to move to a new junction box.
>
> > Assuming the circuit is 20 amp, could I get new cable and splice the
> > white/white, black/black, and ground/ground inside the old junction
> > box, and then run the cable the 8 inches up the wall into a new "old
> > work" blue plastic junction box for a light fixture? I'd get a cover
> > for the old junction box, and our medicine cabinet would conceal it so
> > it would still be accessible as per code, but not viewable every day.
> > I'd then follow the lighting fixture guidlines for coupling the white/
> > white and black/black, but how would I handle the ground? The
> > instructions are to put the fixture's ground wire to the screw, but
> > then what would I do with the ground from the extension cable?
>
> > Thanks if you made it through this long question.
>
> In the 1960's it was not required to have a 20 amp circuit for the bathroom.
> Nor for the kitchen for that matter. The current code does require a 20 amp
> circuit for the bathroom GFCI outlet and you can leave the lighting on the
> existing circuit. Since you are redoing the bathroom it is a good idea to
> bring it up to current standards.
>
> Your plan to redo the light box sounds good. Do what the other poster said
> with the grounds.- Hide quoted text -
>
> - Show quoted text -
Mike and John,
We bought the new 12-gauge Romex and hooked up the fixture by the plan
and taking your advice about the grounds. The circuits in our house
luckily were all brought up to standard some time before we bought the
house, so we did have a 20 amp circuit for the bathroom already. Now
we just have to repair the giant hole where the old inset medicine
cabinet was, and prime and paint. Thanks again!
Layne
|
| Similar Threads | Posted | | Electrical - Wiring a sconce from a valence | December 29, 2005, 2:20 pm |
| Bathroom Electrical Question | August 7, 2006, 11:36 am |
| Adding new bathroom in basement - electrical question | February 25, 2007, 3:01 pm |
| Adding or moving an electrical outlet | October 5, 2006, 1:43 pm |
| Sconce lighting | October 2, 2006, 10:55 pm |
| Wall Sconce Recall | March 21, 2007, 5:33 pm |
| LED bed lamp or wall sconce? | June 30, 2008, 11:54 am |
| You Light Up the Room - Wall Sconce | September 30, 2008, 1:48 pm |
| Have a question regarding moving a washer machine or dryer | December 28, 2005, 7:17 pm |
| Question :moving a small outdoor central air conditioning unit | February 23, 2007, 9:58 am |
|
|