Rick F <rickf@ca-flower.com> wrote:
> Hi all..
> In our house we bought about 4 years ago, we've recently had occasional
> power glitches on 1/2 of the house consisting of multiple circuits.
> This particular part of the house was remodeled about 13 years ago and
> had lots of electrical work done at the time including an upgraded new
> panel (200A).
It's not clear to me if this is a new sub-panel, or was the main
house panel upgraded? In either case it sounds like one side of
the 220V main has a loose connection or possibly a bad main breaker
or meter. The loose connection is most likely and you should have
the power company check for that, or an electrician, though I guess
you have to get the power company out to reseal the box anyway.
Bill Ranck
|
|